Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a 23 2.3.11
GP Dimming Panels
GRAFIK Systems
®
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambienttemperature
willbe0-40°C(32-104°F).
•Thisequipmentisaircooled.Donotblockventsorwarranty
will be void. Leave 12 in (310 mm) clearances above, below,
and in front of Panel. Leave clearance on sides for NEC®
Class 2/PELV wiring.
•Reinforcewallstructureforweightandlocalcodes.
Wiring Raceway
Feed
Wiring
air
flow
Load
Circuit
Wiring
Main Lugs or
MainBreaker.
TerminalBlocks
for Load Circuits
12 in
(310 mm)
minimum
top and front
12 in
(30 mm)
minimum
GP8-24 Front View GP8-24 Side View
For maximum Feed and Wire Sizes,
consult Wiring Overview page.
•DimmingPanelswillhumslightlyandinternalrelayswillclick
while in op er a tion. Mount where audible noise is ac cept able.
•MountPanelssoline(mains)voltagewiringisatleast6ft
(1.8 m) from sound or electronic equipment and wiring.
•GPPanelsmustbemountedwithin7°oftruevertical.
NEC® Class 2/
PELV Wiring
GP8-24 Standard-Size Panel Mounting
Panel
GP8
GP12
GP16
GP20
GP24
Maximum
BTUs/Hour
1365
2045
2725
3405
4085
Weight
(withoutpackaging)
115lbs(52kg)
130lbs(59kg)
145lbs(66kg)
160lbs(73kg)
175lbs(80kg)
Notice: Water damages Panels. Install where they will not get wet.