Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a252.3.11
GP Dimming Panels
GRAFIK Systems
®
NEC® Class
2/PELV Wiring
Terminal
Blocks
for Load
Circuits
Main
Lugs
or Main
Breaker
Feed and
Load
Circuit
Wiring
Raceway
GP36
GP48-72
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambient
temperaturewillbe0-40°C(32-104°F).
•Thisequipmentisaircooled-donotblockvents
or warranty will be void. Leave 12 in (310 mm)
clearances above and in front of Panel. Leave
clearance on sides for NEC® Class 2/PELV wiring.
GP36-72
Side View
12 in
(310 mm)
minimum
top and
front
air
flow
Wall
Ceiling
•MountPanelonfloorandagainstawall.
Use 1/2 in (13 mm) mounting bolts.
•DimmingPanelswillhumslightlyand
internalrelayswillclickwhileinoperation.
Mount where audible noise is ac cept able.
•MountPanelssoline(mains)voltagewiring
is at least 6 ft (1.8 m) from sound or
electronic equipment and wiring.
•GPPanelsmustbemountedwithin7°of
true vertical.
GP36-72 Mounting
GP36 consists of the right side module only. Mount
as shown.
GP96-144 Mounting
•Allowairflowand3ft(92cm)clearancefrom
fronts/sides of panel as shown.
•NotetheextraNECClass2(IECPELV)wiring.
Alternate Conduit Locations
•RunFeedWiringinfrombottom.
•RunLoadCircuitWiringinfromleftside.
GP36-144 Large-Size Panel Mounting
Panel
GP36
GP48
GP60
GP72
GP96-144
Maximum
BTUs/Hour
4350
5800
7250
8700
17400
Weight
(withoutpackaging)
325lbs(147kg)
550lbs(250kg)
600lbs(273kg)
650lbs(295kg)
1300lbs(590kg)
GP96-144
12 in
(310 mm)
min.
12 in
(310 mm)
min.
3 ft
(930 mm)
min.
3 ft
(930 mm)
min.
NEC® Class 2/
PELV Wiring
air
flow
air
flow
Front View
Front View
Side View (Right)
Ceiling
Raceway
Feed and
Load Circuit
Wiring
Main Lugs
or Main
Breaker
NEC
® Class
2/PELV
Wiring
Terminal
Blocks
for Load
Circuits
Wall
Notice: Water damages Panels. Install where
they will not get wet.