Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a352.3.11
GP Dimming Panels
GRAFIK Systems
®
GP36-GP144 Large-Size Panels Wiring Overview
Feed Wiring
TerminalBlock
Load Neutral
Load
DimmedHot/Live
BranchCircuitBreakers
NEC® Class 2/PELV wiring
PowerFeed(Hot/Live)
Varies depending on MB or MLO.
See model numbers page.
Neutral Feed
Varies depending on MB or MLO.
See model numbers page.
Bypass
Jumpers
Do Not
Remove
Typical Load Circuit
Wiring Tips
Wire the GP36-144 similar to wiring a lighting
Distribution Panel:
•Runfeedandloadwiring.Nootherwiringor
assembly required.
•CommonNeutralsarenotpermitted.Runsepa-
rate Neutrals for each load circuit.
The GP36-144 can provide temporary lighting:
•Wireallloads.
•Donotremovethebypassjumpersthatprotect
the Dimming Modules.
•UseBranchCircuitBreakerstoswitchlightson
and off.
Wire Sizes
•FeedWiring:
Panel Feed Wire Sizes
MainLugsOnly Parallel4AWGto500KCMIL(MCM)
200A-400AMainBreakers 1/0AWG(50mm
2
) to 600 KCMIL (MCM)
•DimmedHot/Live:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•LoadNeutral:
14 AWG (2.0 mm
2
) to 6 AWG (10.0 mm
2
)
Power Equipment