Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a 34 2.3.11
GP Dimming Panels
GRAFIK Systems
®
Wiring Tips
Wire the GP8-24 similar to wiring
a lighting Distribution Panel:
•Runfeedandloadwiring.Noother
wiring or assembly required.
•CommonNeutralsarenot
permitted. Run separate Neutrals
for each load circuit.
The GP8-24 can provide
temporary lighting:
•Wireallloads.
•Donotremovethebypassjumpers
that protect the Dimming Modules.
•UseBranchCircuitBreakers
to switch lights on and off.
GP8-24 Standard-Size Panel Wiring Overview
220-240 V
DL
1
SL
1
L
1
DL
2
SL
2
L
2
N
1
N
1
TerminalBlock
Load Neutral Dimmed Live
Branch
Circuit
Breakers
Bypass Jumpers
Do Not Remove
Typical Load Circuit
Load
Feed Wiring
Neutral Feed
Power Feed
(Hot/Live)
Wire Sizes
•PowerFeed:
14 AWG (2.0 mm
2
)to2AWG(35.0mm
2
)
•NeutralFeed:
14 AWG (2.0 mm
2
)to2AWG(35.0mm
2
)
•DimmedHot/Live:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•LoadNeutral:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
NEC® Class 2/
PELV wiring